Quantcast
 
 
  Search
 
 
 
  STANDARD PRS SYSTEMS  
 
Telecom Production Area
 

Magnetek's Standard PRS systems are pre-configured power systems sized from 9 Amps to 200 Amps Redundant.  The batteries used in the systems are either Power Battery or C & D Dynasty batteries.  Additional vendors, with equivalent or superior product, may be added to this list.  Magnetek's pre-configured Standard Power Systems can generally be shipped in 2 - 4 weeks.

The power systems categorized below contains a selection chart that provides Model Numbers and Part Numbers to aid in identifying and ordering the systems.  The Part Number is very specific and should be used for purchase orders. The Model Number describes the major system components and is useful for discussing your equipment with systems engineers or maintenance personnel.

 

The PRS system matrices are separated by battery backup time ---- 1 Hour, 2 Hours, 4 Hours, or 8 Hours.  These pre-configured power systems are sized from 9 Amps to 200 Amps Redundant.  For larger systems please contact Technical Sales Engineers at 1-800-443-4742.

To view system drawing, click on the hyperlink below.

* R = redundant systems      PRS System Dimensions = 24"W x 15"D x 84" H

SYSTEM
AMPS*
MAX
LOAD
MODEL NUMBER PART # EST.
WT.
LBS.
EST.
FLOOR
LOAD
lbs/ft
BTUs AC CIRC. CURRENT
PER AC
CIRCUIT
VOLTAGE
1 HOUR BACKUP (24 Hour Recharge)
9A 8.20 PRS48-1G30MA9B5 A012445
9A R 9.00 PRS48-1G30MA9B5R A012446
15A 14.50 PRS48-1G30MA15B5 A012447
20A 19.75 PRS48-1G30MA20B5 A012448 315 105 979 1 16A max 110, 120
20A R 20.00 PRS48-1G30MA20B5R A012449 325 108 979 2 16A max 110, 120
25A 24.38 PRS48-1G45MA25B5 A012450 370 122 778 1 16A max 208, 240
25A R 25.00 PRS48-1G45MA25B5R A012451 375 125 778 2 16A max 208, 240
50A 48.75 PRS48-1G90MA50B5 A012452 525 175 1,181 1 16A max 208, 240
50A R 50.00 PRS48-1G90MA50B5R A012453 520 174 1,556 3 16A max 208, 240
75A 73.54 PRS48-1G125MA75B5 A012454 635 212 2,334 3 16A max 208, 240
75A R 75.00 PRS48-1G125MA75B5R A012455 645 215 2,334 4 16A max 208, 240
100A 97.50 PRS48-2G90MA100B5 A012456 875 292 2,362 2 16A max 208, 240
100A R 100.00 PRS48-2G90MA100B5R A012457 890 297 2,362 3 16A max 208, 240
150A 150.00 PRS48-2G90MA150B6 A012458 890 297 3,543 3 16A max 208, 240
150A R 150.00 PRS48-2G90MA150B6R A012459 905 302 3,543 4 16A max 208, 240
200A 194.38 PB48MA200B7RS48
-3G125
240
1,340
79
412
4,725 4 16A max 208, 240
200A R 200.00 PB48MA200B7RRS48
-3G125
260
1,340
87
412
4,725
5 16A max 208, 240
Back to Top
SYSTEM
AMPS*
MAX
LOAD
MODEL NUMBER PART # EST.
WT.
LBS
.
EST.
FLOOR
LOAD
lbs/ft
BTUs AC
CIRC.
CURRENT
PER AC
CIRCUIT
VOLTAGE
2 Hour Backup(24 Hour Recharge}
9A 8.20 PRS48-1G30MA9B5 A012445
9A R 9.00 PRS48-1G30MA9B5R A012446
15A 13.88 PRS48-1G45MA15B5 A012460
20A 18.08 PRS48-1G70MA20B5 425 142 979 1 16A max 110, 120
20A R
20.00 PRS48-1G70MA20B5R A012462 435 145 979 2 16A max 110, 120
25A 23.33 PRS48-1G70MA25B5 A012463 425 142 778 1 16A max 208, 240
25A R 25.00 PRS48-1G70MA25B5R A012464 435 145 778 2 16A max 208, 240
50A 47.29 PRS48-1G125MA50B5 A012465 635
212
1,181 1 16A max 208, 240
50A R
50.00 PRS48-1G125MA50B5R A012466 630 210 1,556 3 16A max 208, 240
75A 68.33 PRS48-2G125MA75B5 A012467 1,080 360 2,334 3 16A max 208, 240
75A R 75.00 PRS48-2G125MA75B5R A012468 1,090 365
2,334
4 16A max 208, 240
100A
94.58
PRS48-2G125MA100B5 A012469 1,100
366
2,362 2 16A max 208, 240
100A R 100.00 PRS48-2G125MA100B5R A012470 1,115
372
2,362 3 16A max 208, 240
150A 141.88 PB48MA150B6RS48
-3G125
A011596 A012065 220
1,340
74
412
3,543 3 16A max 208, 240
150A R 150.00 PB48MA150B6RRS48
-3G125
A011597 A012065 240
1,340
79
412
3,543 4 16A max 208, 240
200A 195.00 PB48MA200B724
-90A11
A011598
24-90A11
240
1,908
79
382
4,725 4 16A max 208, 240
200A R 200.00 PB48MA200B7R24
-90A11
A011599
24-90A11
260
1,908
87
382
4,725 5 16A max 208, 240
Back to Top
SYSTEM
AMPS*
MAX
LOAD

MODEL
NUMBER

PART # EST.
WT.
LBS.
EST.
FLOOR
LOAD
lbs/ft
BTUs AC
CIRC.
CURRENT
PER AC
CIRCUIT
VOLTAGE
4 Hour Backup (24 Hour Recharge)
9A 7.58 PRS48-1G45MA9B5 A012471
9A R 9.00 PRS48-1G45MA9B5R A012472
15A 12.83 PRS48-1G70MA15B5 A012473
20A 17.25 PRS48-1G90MA20B5 A012474 505 168 979 1 16A max 110, 120
20A R 20.00 PRS48-1G90MA20B5R A012475 515 171 979 2 16A max 110, 120
25A 21.04 PRS48-1G125MA25B5 A012476 615 205 778 1 16A max 208, 240
25A R 25.00 PRS48-1G125MA25B5R 625 208 778 2 16A max 208, 240
50A 42.08 PRS48-2G125MA50B5 A012478 1,085 361 1,181 1 16A max 208, 240
50A R 50.00 PRS48-2G125MA50B5R 1,085 361 1,556 3 16A max 208, 240
75A 63.75 PB48MA75B5RS48
-4G90
190
1,330
63
409
2,334 3 16A max 208, 240
75A R 75.00 PB48MA75B5RRS48
-4G90
200
1,330
66
409
2,334 4 16A max 208, 240
100A 84.17 PB48MA100B5RS48
-4G125
205
1,770
69
545
2,362 2 16A max 208, 240
100A R 136.67 PB48MA100B5RRS48
-4G125
220
1,770
74
545
2,362 3 16A max 208, 240
150A 127.50
PB48MA150B624-90A17
A011596
24-90A17
220
3,008
74
752
3,543 3 16A max 208, 240
150A R 150.00 PB48MA150B6R24
-90A17
24-90A17
240
3,008
79
752
3,543 4 16A max 208, 240
200A 180.00 PB48MA200B724
-90A21
24-90A21
240
3,648
79
768
4,725 4 16A max 208, 240
200A R 200.00 PB48MA200B7R24
-90A21
24-90A21
260
3,648
87
768
4,725 5 16A max 208, 240
Back to Top
SYSTEM
AMPS*
MAX
LOAD
MODEL NUMBER PART # EST.
WT.
LBS.
EST.
FLOOR
LOAD
lbs/ft
BTUs AC
CIRC.
CURRENT
PER AC
CIRCUIT
VOLTAGE
8 Hour Backup (24 Hour Recharge)
9A 6.53 PRS48-1G70MA9B5 A012480
9A R 9.00 PRS48-1G70MA9B5R A012481
15A 10.54 PRS48-1G125MA15B5 A012482
20A 13.50 PRS48-2G90MA20B5 A012483 840 280 979 1 16A max 110, 120
20A R 20.00 PRS48-2G90MA20B5R A012484 850 283 979 2 16A max 110, 120
25A 15.83 PRS48-2G125MA25B5 A012485 1065 355 778 1 16A max 208, 240
25A R 25.00 PRS48-2G125MA25B5R A012486 1075 358 778 2 16A max 208, 240
50A 33.75 PB48MA50B5RS48
-5G90
A011590
A012066
190
1760
63
542
1,181 1 16A max 208, 240
50A R 50.00 PB48MA50B5RRS48
-5G90
190
1760
63
542
1,556 3 16A max 208, 240
75A 52.71 PB48MA75B5RS48
-5G125