Quantcast
 
 
  Search
 
 
 
  STANDARD POWER SYSTEMS - PB SYSTEMS  
 
Telecom Production Area
 

The pre-configured systems below are sized from 9 Amps to 200 Amps Redundant.  For larger systems please contact Technical Sales Engineers at 1-800-443-4742. Magnetek's pre-configured Standard Power Systems can generally be shipped in 2 - 4 weeks.

A battery backup system can be used with all Magnetek PB systems.  To select the appropriately sized battery system use the selection matrices found in the Batteries and Backup SolutionsSystems product information section.

To view system drawing, click on the hyperlink below.

* R = redundant systems          PB System Dimensions = 24"W x 15"D x 84" H
SYSTEM
AMPS*
MODEL
NUMBER
PART #
EST.
WEIGHT
(lbs)
EST.
FLOOR
LOAD
(lbs/ft2
)
BTUs
AC
CIRC.
CURRENT
PER AC
CIRCUIT
VOLTAGE
9A PB48MA9B5 A011583
9A R PB48MA9B5R A011584
15A PB48MA15B5
A011585
20A PB48MA20B5 A011586
170
57
979
1
16A max
110, 120
20A R
PB48MA20B5R
180
60
979 2 16A max
110, 120
25A
PB48MA25B5 A011588
170
57
778 1 16A max 208, 240
25A R
PB48MA25B5R A011589
180
60
778 2 16A max 208, 240
50A
PB48MA50B5 A011590
190
63
1,181 1 16A max 208, 240
50A R
PB48MA50B5R A011591
190
63
1,556 3 16A max 208, 240
75A PB48MA75B5 A011592
190
63
2,334 3 16A max 208, 240
75A R
PB48MA75B5R A011593
200
66
2,334 4 16A max 208, 240
100A
PB48MA100B5 A011594
205
69
2,362 2 16A max 208, 240
100A R
PB48MA100B5R A011595
220
74
2,362 3 16A max 208, 240
150A
PB48MA150B6
220
74
3,543 3 16A max 208, 240
150A R PB48MA150B6R
240
79
3,543 4 16A max 208, 240
200A
PB48MA200B7 A011598
240
79
4,725 4 16A max 208, 240
200A R
PB48MA200B7R A011599
260
87 4,725 5 16A max 208, 240

 
 
 
© 2008 MAGNETEK, INC.

Overview | DC Power Systems | Batteries & Backup Solutions | Parts & Accessories | Indoor Cabinets
Outdoor Enclsoures | Mobile Communications Solutions | Monitoring Equipment | Power Distribution Products
Literature Request | Manuals | Brochures | Warranty | News | Events | Technical Support | Magnetek | Contact Us