POWER PLANT 1500-3000 Amp, -48VDC MODULAR POWER SYSTEM |
|
|
 |
|
|
|
 |
| |
|
The Magnetek power platform is a modular power system providing up to 3000 Amps power for -48V systems, using Magnetek's 50 Amp rectifiers.
- Plug 'n play technology allows for easy system configuration. System capacity can be increased by simply plugging additional rectifiers into the existing mounting space in the power bay. No set-up or adjustment is required. The Magnetek platform design allows the user to appropriately size a power plant up to 3000 Amp and provide load power, battery float current and battery recharge current.
- The components of this Magnetek power system includes the control unit, the 48V-50A rectifier modules and the supplemental distribution bay.
- Each power bay can accommodate up to 30 rectifiers (Standard Version) providing 1500 Amps of DC power and is capable of controlling them through the control unit which monitors the entire power system.
|

Brochure |
Overview
- Modular design: the standard 1500 Amp cabinet houses up to 30 of the 48V 50 Amp rectifiers - or up to 60 rectifiers of the 48V 50 Amp in the expanded 3000 Amp version.
- The output current is up to 1500 Amp (48V) for the Standard version and it is expandable to 3000 Amp (48V).
- Input voltage: single phase 176 - 264Vac, 50 or 60 Hz.
- Rectifier hot pluggability.
- Run-time automatic reconfiguration recognition.
- Full parameter programmability.
- Connectable to four battery strings with battery disconnect.
- Supplemental Distribution Bay:
- Width: 30.5"(770mm) x Depth: 27" (685mm) x Height: 84" (2130mm).
- Rectifier cabinet dimensions (same size for main cabinet and expansion cabinet) Width: 24.5"(620mm) x Depth: 27" (685mm) x Height: 84" (2130mm)
Features
- For all Telecommunication applications.
- Lower side AC input access, battery connection and outputs.
- Complete control and supervision via Magnetek's power system controller.
- Cost effective design.
- Easy installation and maintenance.
- Connectivity through: RS232, Modem (internal), Ethernet
General
| Mechanical Parameters |
| Power Bay |
Width: 24.5"(622mm) x Depth: 27"(685mm) x Height: 84"(2130mm) |
| Main Distribution Cabinet |
Width: 30.5"(774mm) x Depth: 27"(685mm) x Height: 84"(2130mm) |
| Rectifier weight |
13.28 lbs. (6.04 kg) |
| Power bay weight |
450 lbs. (223 kg) |
| Supplemental bay weight |
650 lbs. (294 kg) |
| Environmental |
| Operating Temperature Range |
-40°F to 140°F (-40°C to +60°C) |
| Storage Temperature |
-40°F to +185°F (-40°C to + 85°C) |
| Cooling |
Forced (fan housed into rectifiers) |
| EMC |
EN55022 class B |
Protection and Sensing
- 16 individual pullouts for load distribution outputs
- 4 battery disconnects
- Battery voltage and current sensing
- Load voltage and current sensing
The System Components
Power Conversion Unit – Magnetek Enhanced Series 48V/50A Rectifier
| Input Parameters |
| Input voltage range |
176-264 Vac |
| Input frequency |
47-63 Hz |
| Input current |
<20 Arms |
| Inrush current |
30 Apk |
| Power factor |
0.99 (above half load, 230 Vac) |
| Efficiency |
92% |
| EMI |
EN55022 class "B" |
| Turn on delay |
(*) 1 sec. |
| Output Parameters |
| Output voltage range |
40-60Vdc |
| Equalize voltage |
(*) 56V |
| Floating voltage |
(*) 54.4V |
| Output current |
50 Amp |
| Output power |
3000W max. continuous |
| Hold-up time |
20msec 176Vac, full load |
| Voltage regulation |
+/-0.4% |
| Output current walk-in time |
(*) 10 sec |
| Output voltage rise time |
(*) 500 msec |
| Overcurrent protection type |
constant current limitation |
| Overcurrent and ShortcircuitLimitation |
constant current limitation |
| Overcurrent and ShortcircuitLimitation |
55 Amp |
| Overvoltage protection |
two levels of protection. Latch up mode |
| Catastrophic OV |
65V |
| First OV threshold |
(*) 61.5V |
| Overtemperature protection |
shutdown with self-recovery |
| Overtemperature threshold |
230°F(110°C) on most critical internal component |
| Current sharing precision |
2% |
| Alarms |
fan failure, OV, OT, UV, OC |
| MTBF |
150,000 hours at 122° F (50° C) |
| Environmental |
| Cooling |
By two internal fans. In case of a single fan failure, the alarm is triggered and the output current limitation lowered to 50% for continuous operation. |
| Operating temp. range |
14°F to +140°F (-10°C to 60°C) fully operational40°F to 14°F (-40°C to - 10°C) start up with LC |
| Safety standards |
UL, CSA & IEC certified Complies to Bell Core standard TR-TSY000947 |
*All specification subject to change without notice |
|