| Output Parameters |
| Output voltage range(*) |
40-60Vdc (48V) 20-30VDC (24V) 56V (48V version) 28V (24V version) |
| Equalize voltage (*) |
54.4V(48) 27.2V(24) |
| Floating voltage (*) |
50A(48V) 100A(24V) |
| Output current |
3000W maximum continuous |
| Output power |
20msec 176Vas, full load |
| Hold-up time |
± 0.4% |
| Output voltage regulation |
200mVpk (48V) 300mVpk (24V);bw: 100MHZ |
| Output PARD |
10 sec. |
| Output current walk-in time (*) |
500msec. |
| Output voltage rise time (*) |
Constant current limitation |
| Over-current protection type (*) |
55A (48V) 110A (24) |
| Over-current and short circuit limitation |
Two levels of protection. Latch up mode. |
| Over-voltage protection Catastrophic OV First OV Threshold |
65V (48V) 32V (24) 61.5V (48V) 30.5 (24V) |
| Over-Temperature protection (OT) |
Shutdown with self-recovery |
| Over-Temperature threshold |
110ºC on most critical internal components |
| Current sharing precision |
2% (48V) 4%(24V) |
| Alarms |
Fan failure, OV, OT, UV, OC |
| Cooling |
By two internal fans. In case of single fan failure alarm is triggered and the output limitation lowered to 50% for continuous operation. |
| MTBF |
150,000 hours at 50ºC |